The early shielded distribution frame used the front column in the cabinet as the bus bar. Because this method will be affected by the quality of the cabinet and may cause grounding connection failure, it is rare to see such a distribution frame now. In the telecom room, if there are multiple cabinets, their grounding wires should also be connected to the grounding piles in the telecom room in a star structure. This form of grounding requires buildings to have as many good grounding points as possible. For buildings that cannot meet this requirement, honeycomb structure is used to make up for it. This kind of local grounding network can be imitated by metal cable channel, double floor or parallel copper wire. Adding grounding wire can reduce the structural size of grounding circuit and weaken the influence of interference signal. However, the design of this prevention and control structure should be combined with high-pressure regulations and safety schemes. Each cabinet shall be connected to the grounding copper bar of the machine room through the grounding wire, and ensure that the grounding resistance of the distribution frame to the ground is less than 1ω. The grounding of the shielded wiring system should be completely separated from the high voltage grounding and connected to the grounding bus at the bottom of the building.