Characteristics of dry steam humidifier
The humidification efficiency is high, reaching more than 95%. All stainless steel material, beautiful and durable. Its unique double-layer steam jacket and silencing structure ensure that the sprayed steam will not spray water, and the steam will not whistle and make noise during flowing and spraying. At the same time, the electric regulating valve, solenoid valve and manual dry steam humidifier can be organically combined into a whole to realize remote and accurate adjustment and control of humidity.
How to install dry steam humidifier
1, which is within the absorption range.
The installation of the humidifier should be within the absorption distance, otherwise a multi-nozzle humidifier should be adopted, and the nozzles should be consistent with the air flow direction.
2. The end is tilted upward
The end of the nozzle should be slightly inclined upward so that the condensed water can flow back to the flash chamber. Nozzle should be installed between heater and muffler as far as possible to eliminate steam injection noise.
3. Keep your distance.
Nozzle should be installed at least 250 mm downstream of surface cooling. Keep a distance of at least 2m between the humidifier nozzle and the control sensing element. When installing multiple nozzles, the nozzle spacing should be equal.
That's all for the dry steam humidifier.