Who can tell me the difference between standard double conversion mode, ECO mode and E conversion mode in Schneider Galaxy VX three-phase UPS?

Yinhe VX is the latest innovative product of Schneider Electric, and also the latest member of Chanruo Qunxing Yinhe series. Yinhe VX is Schneider's most efficient and flexible three-phase uninterruptible power supply so far. It can provide three unique operating modes to help achieve these goals, and each mode provides a proprietary combination of efficiency and performance characteristics to meet the needs of business operations.

These modes are:

Traditional on-line double conversion mode: With the 4-stage technology patented by Schneider, Yinhe VX can provide the whole machine efficiency as high as 96.4% with the lowest component pressure, and improve the reliability of IGBT 10 times;

ECO mode: it is mainly developed for energy saving. In ECO mode, when the bypass is normal, the UPS system supplies power to the load through the bypass and stands by for the inverter. When the bypass voltage/frequency exceeds a certain range, the output of UPS is switched to inverter operation, and the working efficiency can be as high as 99%, which can save electricity by 8% compared with the general UPS operation mode.

E-conversion mode is a unique mode of Schneider UPS: it combines ECO mode and double conversion mode, which can provide high and reliable power quality with efficiency as high as 99%. Compared with the double conversion mode, it can achieve 5% energy saving while obtaining high reliable power quality. In this mode, VX can also be used as an active filter and power factor compensation cabinet. In addition, the E-conversion mode can provide the protection features of the dual conversion mode in an energy-efficient state. I hope I can help you!