8.5. 1 The following places shall be equipped with automatic fire extinguishing systems. Unless it is not suitable for waterproof or fire extinguishing and otherwise specified in this specification, automatic sprinkler system shall be adopted:
1
Opening and cleaning workshop of cotton mills with 50,000 spindles or more; Greater than or equal to 5000
Classification carding workshop of spindle ramie spinning mill; Dry, and screening match factory part; Pre-production, molding, slicing and embossing of foam plastic factory; Woodworking workshop covering an area of more than 1500m2; Covering an area of over 1500m2.
Or the total construction area is more than 3000m2.
Single and multi-storey factories for shoes, clothing, toys and electronic products; High-rise class C factory building; The preparation part of the aircraft engine test bed; The building area exceeds 500m2.
Class C underground workshop;
2 The building area of each building exceeds 1000m2.
Warehouse of cotton, wool, silk, hemp, chemical fiber, fur and its products; Each building covers an area of over 600m2.
Matching warehouses; The building area of the post office building is over 500 square meters.
An empty pouch library; The building area exceeds 500m2.
Underground warehouse of combustible materials; Elevated warehouses and high-rise warehouses for inflammable and flame-retardant articles (except cold storage);
3./kloc-a special, first-class or other theater with more than 0/500 seats; More than 2000
Seating hall or auditorium; A gymnasium with more than 3,000 seats; Lounge and equipment room for indoor staff in sports venues with more than 5,000 people;
four
The construction area of any floor is greater than 1500m2 or the total construction area is greater than 3000m2.
Exhibition buildings, shops and hotels, as well as ward buildings, outpatient buildings and operating departments of the same building scale in hospitals; The building area exceeds 500m2.
Underground shops;
5. Central air conditioning system with air duct (pipe) with a total construction area of more than 3000m2.
Office building, etc. ;
six
Located above four floors underground, semi-underground or above ground, or on the first, second and third floors of a building, and the construction area of any floor is more than 300m2.
Ground song and dance entertainment places (except swimming places);
7 libraries with more than 500,000 books.
The following places should be equipped with automatic fire alarm system:
1
Large and medium-sized computer rooms and their control rooms, recording media libraries, machines, meters, equipment rooms with high fire risk, valuables warehouses and gas fire extinguishing systems;
2
Each building covers an area of over 1000m2.
The warehouse of cotton, wool, silk, hemp, chemical fiber and its fabrics covers an area of more than 500 square meters.
Or a cigarette warehouse with a total construction area greater than 1000m2;
three
The construction area of any floor is greater than 1500m2 or the total construction area is greater than 3000m2.
Shoe-making, clothing, toys and other factories;
4. The construction area of any floor is more than 3000m2.
Or shops, exhibition buildings, finance and trade buildings and passenger and freight buildings with a total construction area of over 6000m2;
five
Collection of books and cultural relics, each library has more than 6.5438+0 million books, which are important files;
six
Radio and television buildings, postal buildings, telecommunications buildings, urban or regional power, transportation and disaster prevention and relief command and dispatch buildings at or above the prefecture level;
7. The number of first-class seats or first-class theater seats exceeds 1500.
Other theaters, cinemas, auditoriums and gymnasiums with more than 2,000 seats;
eight
The building area of the elderly and any floor is greater than 1500m2.
Or hotel buildings, nursing home wards, children's activity places and buildings with a total construction area of more than 3000m2 and a total construction area of 200 or more.
Outpatient building, ward building, operation department, etc. Hospital beds;
9 underground and semi-underground shops with a building area of more than 500m2;
10
Places for singing, dancing, entertainment, projection and entertainment located underground, semi-underground or on the ground of buildings;
1 1 Technical interlayer with clear height greater than 2.6m, more combustible materials and clear height greater than 0.8m.
And there are combustible materials in the stuffy roof or ceiling.