What are the lighting requirements for interior design office space?

Illuminance calculation method:

This method is used to calculate the average illuminance by coefficient method.

Light flux (CU) maintenance factor (MF)/ irradiation area

Utilization coefficient (CU): generally, indoor value is 0.4, and outdoor value is 0.3.

The maintenance coefficient MF=(LLD)X(LDD) is generally 0.7 ~ 0.8.

Example 1:

Indoor lighting, 4× 5m room, 10 sleeve lamp, 2.5 inch 8W energy-saving lamp T428W2.

Average illuminance = total luminous flux of light source ×CU×MF/ area

=(40×8× 10+ 100*28*2)×0.4×0.8÷4÷5

= 140.8 lux

Conclusion: The average illumination is above 120Lux.

General office space lighting requirements:

Hall 300

Elevator room 200

Corridor 200

Office area 300

Meeting area 300-400

Reception area 300